Prevent a Safety automation - relay output card - 8O

Show more characteristics >
  • RRP
    1,068.00 GBP
Add to My Products Remove from My Products

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Relay output card
    safety module name
    XPS MF60
    safety use category
    Category 4 maximum conforming to EN 954-1
    Performance level e conforming to EN/ISO 13849-1
    SIL 3 conforming to EN/IEC 61508
    function of module
    Monitoring safety actuators
    Monitoring safety dialogue
    standards
    DIN V 0801
    DIN V 19250
    EN 50156 pending
    IEC 61131
    [Us] rated supply voltage
    24 V DC (- 15...20 %)
    number of outputs
    8 relay
    connections - terminals
    Removable screw terminal block, clamping capacity: 2 x 0.5 mm²,AWG 20 flexible with cable end
    Removable screw terminal block, clamping capacity: 1 x 0.14...1 x 1.5 mm²,AWG 28...AWG 16 flexible without cable end
    Removable screw terminal block, clamping capacity: 1 x 0.25...1 x 0.5 mm²,AWG 22...AWG 20 flexible with cable end
    Removable screw terminal block, clamping capacity: 1 x 0.25...1 x 1.5 mm²,AWG 22...AWG 16 flexible without cable end
    Removable screw terminal block, clamping capacity: 2 x 0.14...2 x 0.5 mm²,AWG 28...AWG 20 solid without cable end
    Removable screw terminal block, clamping capacity: 2 x 0.14...2 x 0.75 mm²,AWG 28...AWG 18 flexible without cable end
    Removable screw terminal block, clamping capacity: 2 x 0.25...2 x 0.34 mm²,AWG 22 flexible without cable end
    Removable screw terminal block, clamping capacity: 1 x 0.14...1 x 1.5 mm²,AWG 28...AWG 16 solid without cable end
    Complementary
    marking
    CE
    output type
    Relay, with 2 NO per output, volt-free
    contacts material
    Silver alloy, gold flashed
    switching time
    30 ms
    reset time
    20 ms
    contact bounce time
    30 ms
    electrical durability
    >= 250000 cycles
    mechanical durability
    >= 10000000 cycles
    minimum switching voltage
    6 V AC
    maximum switching voltage
    250 V AC
    switching current capacity
    3.15 A / 100 A with internal fuse
    switching capacity in VA
    <= 700 VA, cos f = 1
    switching capacity in W
    <= 40 / <= 70 V
    <= 33 / <= 110 V
    <= 95 / <= 30 V with suitable external fuse
    current consumption
    0.2 A 3.3 V DC rack
    0.7 A 24 V DC power supply
    product weight
    0.6 kg
    Environment
    product certifications
    CSA
    C-Tick
    TÜV
    UL
    IP degree of protection
    IP20 with covering plate on unused in rack I/O card slots
    ambient air temperature for operation
    0...60 °C conforming to EN/IEC 61131-2
    ambient air temperature for storage
    -40...85 °C conforming to EN/IEC 61131-2
    relative humidity
    95 % (supply not connected)
    operating altitude
    < 2000 m
    pollution degree
    2
    electrical shock protection class
    Class II conforming to IEC 61131-2
    electromagnetic compatibility
    EN/IEC 61131-2
    vibration resistance
    1 gn (f = 10...150 Hz) conforming to EN 61131-2 (10 cycles per axis)
    shock resistance
    15 gn for 11 ms (2 cycles per axis), conforming to EN 61131-2
    resistance to electrostatic discharge
    4 kV contact conforming to EN/IEC 61000-4-2
    8 kV on air conforming to EN/IEC 61000-4-2
    resistance to electromagnetic fields
    10 V/m (26...1000 MHz), amplitude modulation 80 % conforming to EN/IEC 61000-4-3
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Preventa safety modular PLC type XPSMF60 (Version 1.0)
    User guide
    Date
    Size
    Add to My Documents
    XPSMF60 Hardware Manual (Version 03)
    Date 13/12/17
    Size 902.6 KB
    Certificate
    Date
    Size
    Add to My Documents
    UL E486184 - NRAQ-NRAQ7 (Version 1.0)
    Date 11/02/19
    Size 395.6 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Dimensions
    Front View


    Max. module depth including screw terminals for the power supply: 239 mm/ 9.21 in.


  • Mounting and Clearance

    Mounting
    Air Circulation