Preventa safety remote mixed I/O module - 8 I not isolated - 4 O not isolated

Show more characteristics >
  • RRP
    2,746.00 GBP
Add to My Products Remove from My Products

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Preventa safety remote mixed I/O module
    safety module name
    XPSMF3
    safety module application
    Extension of I/O capacity
    safety use category
    Category 4 maximum conforming to EN 954-1
    Performance level e conforming to EN/ISO 13849-1
    SIL 3 conforming to EN/IEC 61508
    structure type
    10BASE-T/100BASE-TX
    Complementary
    function of module
    Single-pole measuring of 0 to 10 V voltages
    Closed circuit scanning of input channels
    Measuring, using shunt, 0/4 to 20 mA currents
    [Us] rated supply voltage
    24 V DC (- 15...20 %)
    supply
    SELV or PELV conforming to EN/IEC 60950
    response time
    Depending on size of application
    analogue input number
    8
    analogue input type
    Not isolated
    external resistance
    250 Ohm for analogue input circuit
    500 Ohm for analogue input circuit
    analogue input range
    0...10 V
    0...20 mA with 500 Ohm shunt
    input voltage limits
    0.1...11.5 V
    input current limits
    0.4...23 mA, with 500 Ohm shunt
    analogue input resolution
    12 bits
    safety accuracy
    +/- 2 % for analogue input circuit
    internal input resistance
    <= 500 MOhm for signal source
    2 Ohm
    input overvoltage protection
    -4...15 V
    analogue output number
    4
    analogue output type
    Not isolated
    analogue output range
    4...20 mA
    output current limits
    0...20 mA
    analogue output resolution
    12 bits
    load impedance ohmic
    <= 600 Ohm for analogue output
    relative error
    +/- 1 %
    cable distance between devices
    <= 300 mm analogue input circuit
    <= 300 mm analogue output
    communication port protocol
    Safe Ethernet with 2 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better
    exchange mode
    Half duplex, full duplex, autonegotiation
    number of terminal blocks
    1 for power supply
    5 for analogue input/output circuit
    current consumption
    0.8 A at 24 V DC on power supply
    mounting support
    35 mm symmetrical DIN rail
    depth
    207 mm
    height
    109 mm
    width
    97.5 mm
    product weight
    0.95 kg
    Environment
    IP degree of protection
    IP20 (enclosure)
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C conforming to EN 61131-2
    Contractual warranty
    Warranty period
    18 months
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Presentation

    Housing Elements
    Front View


    No.

    Description

    1

    Power supply input

    2

    Analog inputs

    3

    Analog outputs

    4

    Indicators

    5

    Earth rail

    Top View


    Bottom View



  • Dimensions Drawings

    Dimensions
    Front View


    Side View



  • Mounting and Clearance

    Mounting
    Minimum Clearances


    Air Circulation


    No.

    Description

    1

    The height of the cable ducts is less than 40 mm / 1.57 in.

    2

    The height of the cable ducts is greater than 40 mm / 1.57 in.

    L = H - 40 mm / 1.57 in.

    L = length of the spacer

    H = height of the cable duct

    Minimum clearance when H > 40 mm/1.57 in. and no spacer



    Mounting Precautions Relating to RJ45 Connector


    (1)
    minimum value