Preventa safety remote output relay module - 8 O

Show more characteristics >
  • RRP
    1,764.00 GBP
Add to My Products Remove from My Products

  • Main
    range of product
    Preventa Safety automation
    product or component type
    Preventa safety remote output relay module
    safety module name
    XPSMF2
    safety module application
    Extension of I/O capacity
    safety use category
    Category 4 maximum conforming to EN 954-1
    Performance level e conforming to EN/ISO 13849-1
    SIL 3 conforming to EN/IEC 61508
    function of module
    Monitoring safety actuators
    Monitoring safety dialogue
    [Us] rated supply voltage
    24 V DC (- 15...20 %)
    supply
    SELV or PELV conforming to EN/IEC 60950
    number of outputs
    8 relay
    structure type
    10BASE-T/100BASE-TX
    Complementary
    response time
    Depending on size of application
    associated fuse rating
    10 A, slow-blow
    output type
    Relay, with 2 NO per output, volt-free
    minimum switching voltage
    5 V 250 V AC output relay
    5 V 250 V DC output relay
    switching current capacity
    3 A / 100 A with internal fuse relay output
    switching capacity in VA
    <= 240 VA, cos f = >= 0.5 for relay output
    switching capacity in W
    >= 90 / <= 30 V for relay output
    >= 30 / <= 127 V for relay output
    >= 35 / <= 70 V for relay output
    contacts material
    Silver alloy (Ag/Ni) for relay output
    electrical durability
    >= 250000 cycles for relay output
    mechanical durability
    >= 1000000 cycles for relay output
    communication port protocol
    Safe Ethernet with 2 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better
    exchange mode
    Half duplex, full duplex, autonegotiation
    number of terminal blocks
    1 for power supply
    8 for relay output
    current consumption
    0.6 A at 24 V DC on power supply
    mounting support
    35 mm symmetrical DIN rail
    depth
    86.5 mm
    height
    109 mm
    width
    207 mm
    product weight
    1.3 kg
    Environment
    IP degree of protection
    IP20
    ambient air temperature for operation
    0...60 °C
    ambient air temperature for storage
    -40...85 °C
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Safety remote I/O modules XPSMF1/2/3, for Preventa safety PLCs XPSMF (Version 1.0)
    User guide
    Date
    Size
    Add to My Documents
    XPSMF2DO801 Remote Output Module, Hardware Manual (Version 01)
    Certificate
    Date
    Size
    Add to My Documents
    UL E486184 - NRAQ-NRAQ7 (Version 1.0)
    Date 11/02/19
    Size 395.6 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Presentation

    Housing Elements
    Front View


    No.

    Description

    1

    Power supply input

    2

    Relay outputs

    3

    Indicators

    Top View


    Bottom View



  • Dimensions Drawings

    Dimensions
    Front View


    Side View



  • Mounting and Clearance

    Mounting
    Minimum Clearances


    Air Circulation


    No.

    Description

    1

    The height of the cable ducts is less than 40 mm / 1.57 in.

    2

    The height of the cable ducts is greater than 40 mm / 1.57 in.

    L = H - 40 mm / 1.57 in.

    L = length of the spacer

    H = height of the cable duct

    Minimum clearance when H > 40 mm/1.57 in. and no spacer



    Mounting Precautions Relating to RJ45 Connector


    (1)
    minimum value