on-delay timing relay - 3..300 s - 240 V AC DC - solid state

Show more characteristics >
Commercial status
Discontinued on 01 June 2016
End-of-service on 01 June 2016
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Zelio Time
    product or component type
    Industrial timing relay
    discrete output type
    Solid state
    component name
    RE9
    time delay type
    A
    time delay range
    3...300 s
    Complementary
    width pitch dimension
    22.5 mm
    [Us] rated supply voltage
    24...240 V AC/DC 50/60 Hz
    voltage range
    0.85...1.1 Us
    connections - terminals
    Screw terminals, 2 x 1.5 mm² flexible with cable end
    Screw terminals, 2 x 2.5 mm² flexible without cable end
    tightening torque
    0.6…1.1 N.m
    setting accuracy of time delay
    < +/- 20 %
    repeat accuracy
    < 1 %
    reset time
    100 ms after time delay period
    temperature drift
    <= 0.1 %/°C
    maximum [Ie] rated operational current
    0.7 A at 20 °C
    minimum output current
    10 mA at 20 °C
    overload current
    <= 15 A during 10 ms conforming to VDE 0435 (part 303), 4.8.3/class II
    maximum voltage drop
    <3 V at closed state0.7 A
    maximum leakage current
    6 mA open contact contact(s)
    maximum power dissipation in W
    2.5 W
    electrical durability
    100000000 cycles
    marking
    CE
    overvoltage category
    III conforming to IEC 60664-1
    [Ui] rated insulation voltage
    250 V conforming to IEC
    300 V conforming to CSA
    supply disconnection value
    > 0.1 Uc
    operating position
    Any position without
    surge withstand
    2 kV conforming to IEC 61000-4-5 level 3
    CAD overall width
    22.5 mm
    CAD overall height
    78 mm
    CAD overall depth
    80 mm
    net weight
    0.11 kg
    Environment
    immunity to microbreaks
    100 ms during time delay period
    2 ms after time delay period
    derating factor
    None >20 °C
    standards
    EN/IEC 61812-1
    product certifications
    CSA
    GL
    UL
    ambient air temperature for storage
    -40…85 °C
    ambient air temperature for operation
    -20…60 °C
    relative humidity
    15…85 % 3K3 conforming to IEC 60721-3-3
    vibration resistance
    0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn for 11 ms conforming to IEC 60068-2-27
    IP degree of protection
    IP20 (terminals)
    IP50 (housing)
    pollution degree
    3 conforming to IEC 60664-1
    dielectric strength
    2.5 kV
    non-dissipating shock wave
    4.8 kV
    resistance to electrostatic discharge
    6 kV (in contact) conforming to IEC 61000-4-2 level 3
    8 kV (in air) conforming to IEC 61000-4-2 level 3
    resistance to electromagnetic fields
    10 V/m conforming to IEC 61000-4-3 level 3
    resistance to fast transients
    2 kV conforming to IEC 61000-4-4 level 3
    disturbance radiated/conducted
    CISPR 22 - class A
    CISPR 11 group 1 - class A
    Contractual warranty
    Warranty
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • French
    • Italian
    • German
    Instruction sheet
    Date
    Size
    Add to My Documents
    RE8... /RE9... Electronic Timer (Version 01)
    Date 01/11/04
    Size 790.7 KB
    CAD
    Date
    Size
    Add to My Documents
    CAD for RE9TA21MW: on-delay timing relay - 3..300 s - 240 V AC DC - solid state (Version 1.0)
    CAD file (on TraceParts) for RE9TA21MW: on-delay timing relay - 3..300 s - 240 V AC DC - solid state (Version 2.0)
    End of Life Information
    Date
    Size
    Add to My Documents
    Zelio Time - Timing relay, Product End-of-Life Instructions (Version 1.0)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 22.5 mm
    Rail Mounting


    Screw Fixing



  • Connections and Schema

    Internal Wiring Diagram



    Recommended Application Wiring Diagram


    The timing relay is placed in series, with the load whose energisation is to be delayed on one side and switch K on the other side. The mains supply may be a.c. or d.c. and the voltage may be between 24 V and 240 V.


  • Technical Description

    Function A : Power on Delay Relay
    Description

    The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply


Compare products: /