compact base - 42 + 4 I/O - 24 V DC supply - 2 slots for PCI

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range of product
    Modicon LMC058
    product or component type
    Motion controller
    product specific application
    -
    discrete I/O number
    42
    battery type
    3 V CR2477M lithium battery
    Complementary
    discrete input number
    10 for fast input
    12 for input
    4 for regular input
    discrete input logic
    Sink for fast input
    Sink for regular input
    Source for input
    discrete input voltage
    24 V
    discrete input voltage type
    DC
    analogue input number
    4
    analogue input type
    Current: 0...20 mA
    Current: 4...20 mA
    Voltage: +/- 10 V
    analogue input resolution
    12 bits
    voltage state 1 guaranteed
    >= 15 V for fast input
    >= 15 V for fast output
    >= 15 V for regular input
    voltage state 0 guaranteed
    <= 5 V for fast input
    <= 5 V for fast output
    <= 5 V for regular input
    discrete input current
    4 mA for fast input
    4 mA for regular input
    input impedance
    6 kOhm for fast input
    6 kOhm for regular input
    configurable filtering time
    0 ms for fast input/regular input and fast output
    1.5 ms for fast input/regular input and fast output
    12 ms for fast input/regular input and fast output
    4 ms for fast input/regular input and fast output
    anti bounce filtering
    2 µs...4 ms configurable fast input/regular input and fast output
    maximum cable distance between devices
    <30 m for fast input
    insulation
    Between channels and internal logic at 500 V AC
    Non-insulated between channels
    discrete output number
    12 output
    4 fast output
    discrete output logic
    Source
    discrete output voltage
    24 V DC
    output voltage limits
    19.2...28.8 V
    discrete output current
    4 mA for fast output
    [Us] rated supply voltage
    24 V DC for embedded expert modules power
    supply voltage limits
    20.4…28.8 V
    [In] rated current
    0.04 A for embedded expert modules power
    10 A for I/O power segment
    0.3 A for main supply
    peak current
    100 kA (duration = <= 70 s) for main supply
    25 kA (duration = <= 500 s) for I/O power segment
    50 kA (duration = <= 150 s) for embedded expert modules power
    1.2 A (duration = > 70 s) for main supply
    maximum power consumption in W
    14.14 W
    execution time per instruction
    22 ns Boolean
    memory type
    128 MB flash
    64 MB RAM
    realtime clock
    Without any user calibration clock, clock drift < 30 s/month at 25 °C
    With user calibration clock, clock drift <= 6 s/month
    data backed up
    Battery variables of type retain and retain persistent
    battery life
    1.5 year(s)
    integrated connection type
    1 isolated serial link with female RJ45 connectorModbus with master/slave RTU/ASCII or character mode ASCII, physical interface: RS232/RS485, transmission rate: 300...115200 bps
    1 CAN port with male SUB-D 9 connectorCANmotion bus or CANopen with master
    1 CAN port with male SUB-D 9 connectorCANopen with master
    1 encoder with female SUB-D 15 connector
    1 isolated serial link with female RJ45 connectorEthernet Modbus TCP/IP with slave, physical interface: 10BASE-T/100BASE-TX
    1 isolated serial link with mini B USB connector, transmission rate: 480 Mbit/s
    1 isolated serial link with USB type A connector, transmission rate: 480 Mbit/s
    2 free slots PCI
    transmission rate
    10 kbit/s for bus length of 5000 m for CANopen
    1000 kbit/s for bus length of 4 m for CANopen
    125 kbit/s for bus length of 500 m for CANopen
    20 kbit/s for bus length of 2500 m for CANopen
    250 kbit/s for bus length of 250 m for CANopen
    50 kbit/s for bus length of 1000 m for CANopen
    500 kbit/s for bus length of 100 m for CANopen
    800 kbit/s for bus length of 25 m for CANopen
    counting input number
    8 counting input(s) at 200 kHz
    local signalling
    1 LED for CAN0 STS
    1 LED green/red for CAN1 STS
    1 LED green/yellow for MBS COM
    1 LED per channel for APP0
    1 LED red for APP1
    marking
    CE
    mounting support
    Symmetrical DIN rail
    width
    237.5 mm
    height
    99 mm
    depth
    85 mm
    net weight
    0.77 kg
    Environment
    standards
    UL 508
    IEC 61131-2
    CSA C22.2 No 213
    CSA C22.2 No 142
    product certifications
    CULus
    CSA
    C-Tick
    GOST-R
    ambient air temperature for operation
    0…55 °C without (horizontal installation)
    0…60 °C with derating factor (horizontal installation)
    0…50 °C (vertical installation)
    ambient air temperature for storage
    -25…70 °C
    relative humidity
    5…95 % without condensation
    IP degree of protection
    IP20 conforming to IEC 61131-2
    pollution degree
    2 conforming to IEC 60664
    operating altitude
    0...2000 m
    storage altitude
    0…3000 m
    vibration resistance
    1 gn at 8.4…150 Hz on DIN rail
    3.5 mm at 5…8.4 Hz on DIN rail
    shock resistance
    15 gn for 11 ms
    electromagnetic compatibility
    Electrostatic discharge immunity test - test level: 8 kV (on contact) conforming to EN/IEC 61000-4-2
    Electrostatic discharge immunity test - test level: 4 kV (on air) conforming to EN/IEC 61000-4-2
    Susceptibility to electromagnetic fields - test level: 1 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
    Susceptibility to electromagnetic fields - test level: 10 V/m (80...2000 MHz) conforming to EN/IEC 61000-4-3
    Electrical fast transient/burst immunity test - test level: 1 kV (I/O) conforming to EN/IEC 61000-4-4
    Electrical fast transient/burst immunity test - test level: 1 kV (shielded cable) conforming to EN/IEC 61000-4-4
    Electrical fast transient/burst immunity test - test level: 2 kV (power lines) conforming to EN/IEC 61000-4-4
    Surge immunity test - test level: 0.5 kV (differential mode) conforming to EN/IEC 61000-4-5
    Surge immunity test - test level: 1 kV (common mode) conforming to EN/IEC 61000-4-5
    Conducted RF disturbances conforming to EN/IEC 61000-4-6
    Conducted and radiated emissions conforming to CISPR 11
    disturbance radiated/conducted
    CISPR 11
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    REACh free of SVHC
    Yes
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Toxic heavy metal free
    Yes
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
    Contractual warranty
    Warranty
    18 months
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Motion controller Modicon LMC058 (Version 2.0)
    User guide
    Date
    Size
    Add to My Documents
    Modicon LMC058 Motion Controller, Programming Guide (Version 09)
    SoMachine Compatibility and Migration, User Guide (Version 06)
    CAD
    Date
    Size
    Add to My Documents
    CAD for LMC058LF424: compact base - 42 + 4 I/O - 24 V DC supply - 2 slots for PCI (Version 1.0)
    Certificate
    Date
    Size
    Add to My Documents
    RCM_SupplierDeclarationOfConformity_M258_TM5_TM7 (Version 1.0)
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Modicon DoC M258 LMC058 TM5 (Version 1.4)
    Date 12/10/17
    Size 1.4 MB
    Lexium Declaration of Incorporation MAX - Series (Version 1.1)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 18/08/19
    Size 195.3 KB
    Firmware - Released
    Date
    Size
    Add to My Documents
    M258 LMC058 Firmware (Version 2.0.31.40)
    Date 13/09/18
    Size 815.7 KB
    Date 13/09/18
    Size 6.2 MB
    Date 13/09/18
    Size 6.2 MB
    M258 LMC058 Firmware (Version 4.0.3.6)
    Date 13/09/18
    Size 16.6 MB
    Date 13/09/18
    Size 11.9 MB
    Date 13/09/18
    Size 815.7 KB
    Firmware - Updates
    Date
    Size
    Add to My Documents
    Last Release Notes (Version 4.0.3.6)
    Date 13/09/18
    Size 815.7 KB
    Marine certificate
    Date
    Size
    Add to My Documents
    LR Marine Certificate of Modicon TM258 TM5 LMC058 PLCs (Version 2.0)
    DNV-GL Certificate of TM258, LMC058, TM5 (Version 2.0)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 18/08/19
    Size 195.3 KB
    RoHs China Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Controller
    Dimensions



  • Connections and Schema

    TM5 System Wiring Recommendations
    Wire Sizes to Use with Removable Spring Terminal Blocks



    External Power Supplies
    Wiring Diagram of the Controller Power Distribution Module


    (1)
    Internal electronics
    (2)
    24 Vdc I/O power segment integrated into the bus bases
    (3)
    PS1/PS2: External isolated SELV power supply 24 Vdc
    (4)
    External fuse, Type T slow-blow, 3 A 250 V
    (5)
    External fuse, Type T slow-blow, 2 A 250 V
    (6)
    External fuse, Type T slow-blow, 10 A max., 250 V