    Schneider Eletric LC1D65AFE7 Picture

    Range: TeSys D

    Contactors

    LC1D65AFE7

    Schneider Eletric LC1D65AFE7 Picture
    Range: TeSys D

    Contactors

    LC1D65AFE7

    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 115 V AC 50/60 Hz coil

    Show more characteristics >
    • Price
      184.10 GBP
    Add to My Favourites Remove from My Favourites

    • Main
      range
      TeSys
      product name
      TeSys D
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-1
      AC-3
      AC-4
      poles description
      3P
      pole contact composition
      3 NO
      [Ue] rated operational voltage
      <= 300 V DC for power circuit
      <= 690 V AC 25...400 Hz for power circuit
      [Ie] rated operational current
      80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
      65 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
      motor power kW
      11 kW at 400 V AC 50/60 Hz AC-4
      30 kW at 380...400 V AC 50/60 Hz AC-3
      37 kW at 500 V AC 50/60 Hz AC-3
      37 kW at 660...690 V AC 50/60 Hz AC-3
      18.5 kW at 220...230 V AC 50/60 Hz AC-3
      motor power hp
      40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
      5 hp at 115 V AC 50/60 Hz for 1 phase motors
      10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
      20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
      20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
      50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
      control circuit type
      AC 50/60 Hz
      [Uc] control circuit voltage
      115 V AC 50/60 Hz
      auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      Conforming to IEC 60947
      overvoltage category
      III
      [Ith] conventional free air thermal current
      80 A at <= 60 °C for power circuit
      10 A at <= 60 °C for signalling circuit
      Irms rated making capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      140 A AC for signalling circuit conforming to IEC 60947-5-1
      250 A DC for signalling circuit conforming to IEC 60947-5-1
      rated breaking capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
      100 A 1 s signalling circuit
      120 A 500 ms signalling circuit
      140 A 100 ms signalling circuit
      520 A <= 40 °C 10 s power circuit
      900 A <= 40 °C 1 s power circuit
      110 A <= 40 °C 10 min power circuit
      260 A <= 40 °C 1 min power circuit
      associated fuse rating
      125 A gG at <= 690 V coordination type 1 for power circuit
      125 A gG at <= 690 V coordination type 2 for power circuit
      10 A gG for signalling circuit conforming to IEC 60947-5-1
      average impedance
      1.5 mOhm at 50 Hz - Ith 80 A for power circuit
      [Ui] rated insulation voltage
      600 V for power circuit certifications CSA
      600 V for power circuit certifications UL
      690 V for power circuit conforming to IEC 60947-4-1
      690 V for signalling circuit conforming to IEC 60947-1
      600 V for signalling circuit certifications CSA
      600 V for signalling circuit certifications UL
      electrical durability
      1.45 Mcycles 65 A AC-3 at Ue <= 440 V
      1.4 Mcycles 80 A AC-1 at Ue <= 440 V
      power dissipation per pole
      6.3 W AC-3
      9.6 W AC-1
      protective cover
      With
      mounting support
      Plate
      Rail
      standards
      CSA C22.2 No 14
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      product certifications
      CCC
      CSA
      GOST
      UL
      connections - terminals
      Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
      Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
      Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
      Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end
      Power circuit : screw connection 2 cable(s) 1...25 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end
      Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw connection 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable end
      tightening torque
      Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
      Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
      Power circuit : 8 N.m - on EverLink BTR screw connectors - cable 25...35 mm² hexagonal 4 mm
      Power circuit : 5 N.m - on EverLink BTR screw connectors - cable 1...25 mm² hexagonal 4 mm
      operating time
      12...26 ms closing
      4...19 ms opening
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      6 Mcycles
      operating rate
      3600 cyc/h at <= 60 °C
      Complementary
      coil technology
      Without built-in suppressor module
      control circuit voltage limits
      0.3...0.6 Uc drop-out at 60 °C, AC 50/60 Hz
      0.8...1.1 Uc operational at 60 °C, AC 50 Hz
      0.85...1.1 Uc operational at 60 °C, AC 60 Hz
      inrush power in VA
      140 VA at 20 °C (cos ϕ 0.75) 60 Hz
      160 VA at 20 °C (cos ϕ 0.75) 50 Hz
      hold-in power consumption in VA
      13 VA at 20 °C (cos ϕ 0.3) 60 Hz
      15 VA at 20 °C (cos ϕ 0.3) 50 Hz
      heat dissipation
      4...5 W at 50/60 Hz
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      signalling circuit frequency
      25...400 Hz
      minimum switching current
      5 mA for signalling circuit
      minimum switching voltage
      17 V for signalling circuit
      non-overlap time
      1.5 ms on de-energisation (between NC and NO contact)
      1.5 ms on energisation (between NC and NO contact)
      insulation resistance
      > 10 MOhm for signalling circuit
      Environment
      IP degree of protection
      IP20 front face conforming to IEC 60529
      protective treatment
      TH conforming to IEC 60068-2-30
      pollution degree
      3
      ambient air temperature for operation
      -5...60 °C
      ambient air temperature for storage
      -60...80 °C
      permissible ambient air temperature around the device
      -40...70 °C at Uc
      operating altitude
      3000 m without derating in temperature
      fire resistance
      850 °C conforming to IEC 60695-2-1
      flame retardance
      V1 conforming to UL 94
      mechanical robustness
      Vibrations contactor open 2 Gn, 5...300 Hz
      Vibrations contactor closed 4 Gn, 5...300 Hz
      Shocks contactor open 10 Gn for 11 ms
      Shocks contactor closed 15 Gn for 11 ms
      height
      122 mm
      width
      55 mm
      depth
      120 mm
      product weight
      0.86 kg
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0501  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Product end of life instructions
      Available End of life manual
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      Instruction sheet
      Date
      Size
      Add to My Documents
      CAD
      Date
      Size
      Add to My Documents
      3P EVLK CONT 40A 18,5KW
      Date 19/12/17
      Size 506.4 KB
      Date 19/12/17
      Size 224.2 KB
      Date 19/12/17
      Size 593.4 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Date 21/09/17
      Size 199.4 KB
      Product environmental
      Date
      Size
      Add to My Documents
      Date 09/11/17
      Size 224.4 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
    • Dimensions Drawings

      Dimensions


      (1)
      Minimum electrical clearance

      LC1

      D40A…D65A

      a

      55

      b1

      with LA4 D●2

      with LA4 DB3 or LAD 4BB3

      136

      with LA4 DF, DT

      157

      with LA4 DM, DW, DL

      166

      c

      without cover or add-on blocks

      118

      with cover, without add-on blocks

      120

      c1

      with LAD N (1 contact)

      with LAD N or C (2 or 4 contacts)

      150

      c2

      with LA6 DK10, LAD 6DK

      163

      c3

      with LAD T, R, S

      171

      with LAD T, R, S and sealing cover

      175


    • Connections and Schema

      Wiring



    • Motor Starter BOM

      Our Proposal - Type 1 : Circuit Breaker + Contactor for Motor Power 30 kW and 415 VAC

      Motor power

      (kW)

      ICU

      (kA)

      Breaker

      Contactor (*)

      30

      50


      GV3P65


      LC1D65AFE7

      Non contractual pictures.

      Type 1 coordination requires that in a short-circuit condition, the contactor or starter must not present any danger to personnel or installations and must not be able to resume operation without repair or the replacement of parts.