Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

    Schneider Eletric LC1D65A6MD Picture

    Range: TeSys D

    Contactors

    LC1D65A6MD

    Schneider Eletric LC1D65A6MD Picture
    Range: TeSys D

    Contactors

    LC1D65A6MD

    TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V DC standard coil

    Show more characteristics >
    • Price
      296.06 GBP
    Add to My Favourites Remove from My Favourites

    • Main
      range
      TeSys
      product name
      TeSys D
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-1
      AC-3
      AC-4
      poles description
      3P
      pole contact composition
      3 NO
      [Ue] rated operational voltage
      <= 300 V DC for power circuit
      <= 690 V AC 25...400 Hz for power circuit
      [Ie] rated operational current
      80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
      65 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
      motor power kW
      11 kW at 400 V AC 50/60 Hz AC-4
      30 kW at 380...400 V AC 50/60 Hz AC-3
      37 kW at 500 V AC 50/60 Hz AC-3
      37 kW at 660...690 V AC 50/60 Hz AC-3
      18.5 kW at 220...230 V AC 50/60 Hz AC-3
      motor power hp
      40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
      5 hp at 115 V AC 50/60 Hz for 1 phase motors
      10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
      20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
      20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
      50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
      control circuit type
      DC standard
      [Uc] control circuit voltage
      220 V DC
      auxiliary contact composition
      1 NO + 1 NC
      [Uimp] rated impulse withstand voltage
      Conforming to IEC 60947
      overvoltage category
      III
      [Ith] conventional free air thermal current
      80 A at <= 60 °C for power circuit
      10 A at <= 60 °C for signalling circuit
      Irms rated making capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      140 A AC for signalling circuit conforming to IEC 60947-5-1
      250 A DC for signalling circuit conforming to IEC 60947-5-1
      rated breaking capacity
      1000 A at 440 V for power circuit conforming to IEC 60947
      [Icw] rated short-time withstand current
      100 A 1 s signalling circuit
      120 A 500 ms signalling circuit
      140 A 100 ms signalling circuit
      520 A <= 40 °C 10 s power circuit
      900 A <= 40 °C 1 s power circuit
      110 A <= 40 °C 10 min power circuit
      260 A <= 40 °C 1 min power circuit
      associated fuse rating
      125 A gG at <= 690 V coordination type 1 for power circuit
      125 A gG at <= 690 V coordination type 2 for power circuit
      10 A gG for signalling circuit conforming to IEC 60947-5-1
      average impedance
      1.5 mOhm at 50 Hz - Ith 80 A for power circuit
      [Ui] rated insulation voltage
      600 V for power circuit certifications CSA
      600 V for power circuit certifications UL
      690 V for power circuit conforming to IEC 60947-4-1
      690 V for signalling circuit conforming to IEC 60947-1
      600 V for signalling circuit certifications CSA
      600 V for signalling circuit certifications UL
      electrical durability
      1.45 Mcycles 65 A AC-3 at Ue <= 440 V
      1.4 Mcycles 80 A AC-1 at Ue <= 440 V
      power dissipation per pole
      6.3 W AC-3
      9.6 W AC-1
      protective cover
      With
      mounting support
      Plate
      Rail
      standards
      CSA C22.2 No 14
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      product certifications
      CCC
      CSA
      GOST
      UL
      connections - terminals
      Control circuit : lugs-ring terminals - external diameter: 8 mm
      Power circuit : lugs-ring terminals - external diameter: 16.5 mm
      tightening torque
      Control circuit : 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm screw : M3.5
      Control circuit : 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 screw : M3.5
      Power circuit : 6 N.m - on lugs-ring terminals hexagonal 10 mm screw : M6
      operating time
      16...24 ms opening
      42.5...57.5 ms closing
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      10 Mcycles
      operating rate
      3600 cyc/h at <= 60 °C
      Complementary
      coil technology
      Built-in bidirectional peak limiting diode suppressor
      control circuit voltage limits
      0.1...0.3 Uc drop-out at 60 °C, DC
      0.75...1.25 Uc operational at 60 °C, DC
      time constant
      34 ms
      inrush power in W
      19 W at 20 °C
      hold-in power consumption in W
      7.4 W at 20 °C
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      signalling circuit frequency
      25...400 Hz
      minimum switching current
      5 mA for signalling circuit
      minimum switching voltage
      17 V for signalling circuit
      non-overlap time
      1.5 ms on de-energisation (between NC and NO contact)
      1.5 ms on energisation (between NC and NO contact)
      insulation resistance
      > 10 MOhm for signalling circuit
      Environment
      IP degree of protection
      IP20 front face conforming to IEC 60529
      protective treatment
      TH conforming to IEC 60068-2-30
      pollution degree
      3
      ambient air temperature for operation
      -5...60 °C
      ambient air temperature for storage
      -60...80 °C
      permissible ambient air temperature around the device
      -40...70 °C at Uc
      operating altitude
      3000 m without derating in temperature
      fire resistance
      850 °C conforming to IEC 60695-2-1
      flame retardance
      V1 conforming to UL 94
      mechanical robustness
      Vibrations contactor open 2 Gn, 5...300 Hz
      Vibrations contactor closed 4 Gn, 5...300 Hz
      Shocks contactor open 10 Gn for 11 ms
      Shocks contactor closed 15 Gn for 11 ms
      height
      122 mm
      width
      55 mm
      depth
      120 mm
      product weight
      0.935 kg
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0001  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Product end of life instructions
      Available End of life manual
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      Instruction sheet
      Date
      Size
      Add to My Documents
      CAD
      Date
      Size
      Add to My Documents
      3P EVLK CONT 40A 18,5KW
      Date 19/12/17
      Size 506.4 KB
      Date 19/12/17
      Size 224.2 KB
      Date 19/12/17
      Size 593.4 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Date 21/09/17
      Size 199.4 KB
      Product environmental
      Date
      Size
      Add to My Documents
      Date 09/11/17
      Size 224.4 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.