Welcome to the Schneider Electric Website

Welcome to our website.

You can choose another country to view available products or go to our Global website for company information.

Choose another country or region

    Share

    Copy Cancel
    Schneider Eletric LC1D50F7 Picture

    Range: TeSys D

    Legacy

    LC1D50F7

    Schneider Eletric LC1D50F7 Picture
    Range: TeSys D

    Legacy

    LC1D50F7

    CONTACTOR 600VAC 50AMP IEC +OPTIONS

    Show more characteristics >
    • Price
      180.09 GBP
    Add to My Favourites Remove from My Favourites

    • Main
      range of product
      TeSys D
      range
      TeSys
      product or component type
      Contactor
      device short name
      LC1D
      contactor application
      Motor control
      Resistive load
      utilisation category
      AC-1
      AC-2
      AC-3
      AC-4
      control circuit type
      AC 50/60 Hz
      poles description
      3P
      pole contact composition
      3 NO
      [Ie] rated operational current
      50 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
      80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
      motor power kW
      22 kW at 380...400 V AC 50/60 Hz AC-3
      25 kW at 415 V AC 50/60 Hz AC-3
      30 kW at 440 V AC 50/60 Hz AC-3
      30 kW at 500 V AC 50/60 Hz AC-3
      33 kW at 660...690 V AC 50/60 Hz AC-3
      15 kW at 220...230 V AC 50/60 Hz AC-3
      11 kW at 400 V AC 50/60 Hz AC-4
      30 kW at 1000 V AC 50/60 Hz AC-3
      motor power hp
      15 hp at 200/208 V AC 60 Hz for 3P motors conforming to CSA
      15 hp at 200/208 V AC 60 Hz for 3P motors conforming to UL
      15 hp at 230/240 V AC 60 Hz for 3P motors conforming to CSA
      15 hp at 230/240 V AC 60 Hz for 3P motors conforming to UL
      3 hp at 115 V AC 60 Hz for 1P motors conforming to CSA
      3 hp at 115 V AC 60 Hz for 1P motors conforming to UL
      40 hp at 460/480 V AC 60 Hz for 3P motors conforming to CSA
      40 hp at 460/480 V AC 60 Hz for 3P motors conforming to UL
      40 hp at 575/600 V AC 60 Hz for 3P motors conforming to CSA
      40 hp at 575/600 V AC 60 Hz for 3P motors conforming to UL
      7.5 hp at 230/240 V AC 60 Hz for 1P motors conforming to CSA
      7.5 hp at 230/240 V AC 60 Hz for 1P motors conforming to UL
      [Uc] control circuit voltage
      110 V AC 50/60 Hz
      connections - terminals
      Control circuit : screw clamp terminal 1 cable 1...4 mm² - cable stiffness: solid - without cable end
      Control circuit : screw clamp terminal 2 cable 1...4 mm² - cable stiffness: solid - without cable end
      Power circuit : screw clamp terminal 1 cable 1...35 mm² - cable stiffness: solid - without cable end
      Power circuit : screw clamp terminal 2 cable 1...25 mm² - cable stiffness: solid - without cable end
      Power circuit : screw clamp terminal 1 cable 1...35 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminal 1 cable 1...4 mm² - cable stiffness: flexible - with cable end
      Control circuit : screw clamp terminal 2 cable 1...2.5 mm² - cable stiffness: flexible - without cable end
      Control circuit : screw clamp terminal 2 cable 1...4 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw clamp terminal 2 cable 1...25 mm² - cable stiffness: flexible - with cable end
      Power circuit : screw clamp terminal 2 cable 1...35 mm² - cable stiffness: flexible - without cable end
      Power circuit : screw terminals
      Complementary
      coil technology
      Without built-in bidirectional peak limiting diode suppressor
      protective cover
      With
      auxiliary contacts type
      Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
      Type mirror contact (1 NC) conforming to IEC 60947-4-1
      auxiliary contact composition
      1 NO + 1 NC
      control circuit voltage limits
      0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
      0.8...1.1 Uc at 60 °C operational 50 Hz
      0.85...1.1 Uc at 60 °C operational 60 Hz
      [Ui] rated insulation voltage
      600 V for control circuit certifications CSA
      600 V for control circuit certifications UL
      600 V for power circuit certifications CSA
      600 V for power circuit certifications UL
      690 V for control circuit conforming to IEC 60947-1
      690 V for power circuit conforming to IEC 60947-1
      [Uimp] rated impulse withstand voltage
      8 kV IEC 60947
      overvoltage category
      III
      mounting support
      Plate
      Rail
      flame retardance
      V1 conforming to UL 94
      tightening torque
      Power circuit : 5 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
      Control circuit : 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
      Control circuit : 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
      Power circuit : 5 N.m - on screw clamp terminal - with screwdriver flat Ø 8 mm
      [Ue] rated operational voltage
      <= 690 V AC 25...400 Hz for power circuit
      [Ith] conventional free air thermal current
      10 A at <= 60 °C for control circuit
      80 A at <= 60 °C for power circuit
      Irms rated making capacity
      140 A AC for control circuit conforming to IEC 60947-5-1
      900 A at 440 V for power circuit conforming to IEC 60947
      rated breaking capacity
      900 A at 440 V for power circuit conforming to IEC 60947
      associated fuse rating
      10 A gG for control circuit conforming to IEC 60947-5-1
      100 A gG at <= 690 V coordination type 1 for power circuit
      100 A gG at <= 690 V coordination type 2 for power circuit
      power dissipation per pole
      3.7 W AC-3
      9.6 W AC-1
      inrush power in VA
      140 VA at 20 °C (cos f 0.75)
      160 VA at 20 °C (cos f 0.75)
      hold-in power consumption in VA
      13 VA at 20 °C (cos f 0.3) 60 Hz
      15 VA at 20 °C (cos f 0.3) 50 Hz
      operating time
      12...26 ms closing
      4...19 ms opening
      safety reliability level
      B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
      B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
      mechanical durability
      6000000 cycles
      operating rate
      3600 cyc/h at <= 60 °C
      minimum switching current
      5 mA for control circuit
      minimum switching voltage
      17 V for control circuit
      non-overlap time
      1.5 ms on de-energisation between NC and NO contacts
      1.5 ms on energisation between NC and NO contacts
      insulation resistance
      > 10 MOhm for control circuit
      height
      127 mm
      width
      75 mm
      depth
      119 mm
      product weight
      1.4 kg
      compatibility code
      LC1D
      Environment
      standards
      EN 60947-4-1
      EN 60947-5-1
      IEC 60947-4-1
      IEC 60947-5-1
      UL 508
      CSA C22.2 No 14
      product certifications
      BV
      CCC
      CSA
      DNV
      GL
      GOST
      LROS (Lloyds register of shipping)
      RINA
      UL
      IP degree of protection
      IP2x conforming to IEC 60529
      IP2x conforming to VDE 0106
      ambient air temperature for operation
      -5...60 °C
      ambient air temperature for storage
      -60...80 °C
      permissible ambient air temperature around the device
      -40...70 °C at Uc
      operating altitude
      3000 m without derating in temperature
      fire resistance
      850 °C conforming to IEC 60695-2-1
      shock resistance
      10 gn contactor opened
      15 gn contactor closed
      vibration resistance
      2 gn 5...300 Hz contactor opened
      4 gn 5...300 Hz contactor closed
      heat dissipation
      4...5 W at 50/60 Hz for control circuit
      Offer Sustainability
      Sustainable offer status
      Green Premium product
      RoHS (date code: YYWW)
      Compliant  - since  0001  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
      REACh
      Product environmental profile
      Product end of life instructions
      Contractual warranty
      Warranty period
      18 months
    • Documents and Downloads

      Language
      • English
      • ALL
      CAD
      Date
      Size
      Add to My Documents
      3P EVLK CONT 40A 18,5KW
      Date 19/12/17
      Size 506.4 KB
      Date 19/12/17
      Size 224.2 KB
      Date 19/12/17
      Size 593.4 KB
      Certificate
      Date
      Size
      Add to My Documents
      Date 08/02/18
      Size 2.2 MB
      Declaration of conformity
      Date
      Size
      Add to My Documents
      Date 10/11/17
      Size 52.6 KB
      End of life manual
      Date
      Size
      Add to My Documents
      Date 21/09/17
      Size 199.4 KB
      Product environmental
      Date
      Size
      Add to My Documents
      Date 09/11/17
      Size 224.4 KB
    • Technical FAQs

      No results found.
      Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.