Results 51 - 60 of 100

FAQ ID Description
FA33584Is top cable entry available on Ringmaster
Yes top entry is available on Ringmaster C and Ringmaster Range. More details on Ringmaster C or Ringmaster range.
FA24973What is the ohmic tripping value of a PTC probe on an ATV58?
The motor temperature is detected by PTC probes connected to the ATV58 drive via specific inputs (+10, AI3A, AI3B and COM) on extension card VW3A58201.   The...
FA23007What is the meaning of the items screen-printed on the setting selector switches of the Micrologic and STR electronic control units.
Standard IEC 60947-2 defines the names of the selector switches. The meanings of the screen-printed items on the selector switches of the trip units...
FA22985How can I find a lost code on Sepam 2000?
To find the lost code on a Sepam 2000 prior to 96/49: go to the control logic in which the code (password) is given   To find the lost code of a...
FA27970What is the meaning of the terms 2P2d, 3P3d, 4P3d, 4P4d, 4P3d+N/2 and 4P3d+OSN on the Compact NSX circuit-breaker trip units.
The first number corresponds to the number of poles. The second number corresponds to the number of protected poles. The first letter stands for Pole. The...
FA31962If the C60H circuit breaker is locked ON with the MGLA padlocking facility will it still trip under fault conditions.
Yes, All of the miniature circuit breakers have a "trip free" mechanism which enables them to trip under fault conditions even if the handle is locked...
FA27971What is the definition of the term OSN on electronic trip units?
OSN (Over Size Neutral) means that the neutral protection is 1.6 times greater than the phase protection. This type of trip unit is used if there...
FA32392Does top cable entry affect the IP rating of Ringmaster
Yes top entry reduces the IP rating to IP41 and can only be installed inside a substation.
FA141626What replaced XPSAPF? What are the differences between XPSAPF and the new XPSAK?
XPS-APF Replaced by XPS-AK   XPSAPF (old model)                                                                 XPSAK (new model) XPS-AK...
FA141633What replaced XPSAPF? What are the differences between XPSAPF and the new XPSAR?
XPS-APF replaced by XPS-AR  XPSAPF (old model)                                                    XPSAR (new model) XPS-AR has 2 extra solid...