| FA24892 | How can I distinguish thermal from magnetic faults when using GV2ME, GV2P, GV2L and GV2LE? Using a GVAM11 combined with a GVAD10xx, it is possible to distinguish between thermal and and magnetic faults.
If there is no fault:
GVAM11:... |
| FA23919 | What are the values of the 1P breaking capacities of GV2P circuit-breakers in IT earthing system? The values below are the breaking capacities of GV2P circuit-breakers operating on an IT earthing system at 400 V 50 Hz, as demonstrated by pole-by-pole... |
| FA23169 | How can I automatically address a slave on an ASI bus without a pocket programmer? It is possible to modify an ASI configuration to add a new slave without having an XZMC11 or ASITERV2 pocket programmer.
The ASI module automatic... |
| FA22881 | Can I control a motor with a rating lower than that of the variable speed drive?
Yes it is possible to use a motor with a lower rating than that of the drive.
For instance If you are trying to test a system with either a very... |
| FA23859 | How can I know whether an AS-i product has standard or extended addressing? To find out whether the addressing of an AS-i product is:
standard
extended
Simply check the value of the AS-Interface profile's second... |
| FA22753 | How do I set up an ATS01? Potentiometers
There are 3 potentiometers graded from A to E, but not graded in either seconds or Volts, which can be confusing to customers.
Start... |
| FA23736 | What is the heat loss of the GV2 P / ME /RT thermal magnetic circuit-breakers? The heat dissipation of GV2P/ME/RT circuit breakers is 2.5 W per pole, i.e. 7.5 W in total. |
| FA28027 | Which combination block is used for circuit-breaker and contactor on the LAD311 mounting plates? Between the following two products both mounted on the LAD311 plate:
GV2ME/GV2P circuit-breakers,
TeSys D range contactors: LC1D09-LC1D38,
the... |
| FA86455 | How do I set the target value on an electromechanical Preset Counter? XBKP50100D*0M
There is a button under each digit and reset button to the left of the display. Press the reset button and the button under the digit... |
| FA86416 | The NSX MCCB trips as soon as it's switched on and the display indicates ENCT or STOP If a 3 pole NSX MCCB is fitted with a Micrologic 5 or 6 trip unit the neutral conductor can be protected with an external CT.
If the neutral protection... |