Programming - FAQs

FAQ Search
Most Recently Published FAQs

Results 1 - 10 of 100

FAQ ID Description
FA12064 How to change page resolution in configured project of Vijeo Citect.
S    In order to change the resolution of the pages in Vijeo Citect project do following things:          1. Add the following INI parameter through...
FA245102My Conext CL is not providing accurate data on Modbus.
At low power settings, the inverter may report inaccurate measurements on the Modbus interface. In version 2.04.14, we have added a low pass filter...
FA230070How is the ATV312 default display changed to show a different monitored parameter?
Issue: How is the ATV312 default display changed to show a different monitored parameter? Product Line: ATV312  ATV31 Environment: All Cause: Preference...
FA32789Which "Symbol database" file types should be used with OFS for Unity Premium PLCs?
When using Aliases in OFS, pointing to a Unity Premium PLC, only two types of "Symbol database" file can be used: either user files (.STU), or project...
FA86405How can a Sepam Relay series 80 be configured to use a customized tripping curve?
To create and implement a customized tripping curve for a particular protection function, SFT2841 software is required. The protection functions capable...
FA86406What is the difference between "Sum 3I" and "Input Io" when setting the ANSI 50/51N protection in a Sepam relay?
When setting the ANSI 50/51N protection, the Sepam relay provides 2 different options for residual current type: "Sum 3I" and "Input Io". The residual...
FA86404How do you separate the ANSI 50 (Instantaneous phase overcurrent) from the ANSI 51 (delayed phase overcurrent) protection?
The ANSI 50/51 protection option in SEPAM relays combine both ANSI 50 instantaneous phase overcurrent protection and ANSI 51 delayed phase overcurrent...
FA35832Can Remote Control be enabled from the advanced UMI of the Sepam Series 20, 40 and 80 Relay?
For the Sepam Series 20 and 40 relay "remote control" can be activated by navigating through the front face of the Sepam relay. Go to general settings...
FA36149How many samples per cycle are captured for the Sepam Series 20, 40 and 80? How many samples are used for protection, measurement, and waveform display?
The Sepam protection relay samples at 36 samples per cycle to calculate true RMS values for displayed phase current and overload protection. It can...
FA35830Question Why does the Sepam Series 20, 40 and 80 Relay not display waveforms for all phases of current / voltage?
When certain variables are calculated rather than acquired (measured) by Sepam, the waveform associated to those variables is not available. Those...

Results 1 - 10 of 100